The name of created object | Name of the object created in the Pma object tree.
The maximum name length is 30 characters. This is a system name, so it must contain only alphanumeric and must not contain any diacritics (i.e. national dependent characters), empty string, spaces and first character must not be a number. Default: "S7_comm" |
---|---|
Network address | Network address of the remote device (e.g. of the PLC device), to which the communication will be connected.
The address can be entered as: - IPv4 full address (e.g. "192.168.0.15")
- IPv4 address of this computer (i.e. "127.0.0.1")
- IPv4 computer name (e.g. "server11")
- IPv4 name of this computer (i.e. "localhost")
- IPv6 full address (e.g. "2a02:c38:8136:800a:37a:ab66:6fc9:accd")
- IPv6 address of this computer (i.e. "::1")
Macro expression can be used for input (it is evaluated after the application is launched). After the preconfiguration is created, the "PmaComm > Setting the parameters of the Ethernet-client > Network address" configurator will be set to this value. |
Communication refresh rate [ms] | The period in milliseconds to be used for reading the current data by the PROMOTIC application.
After the preconfiguration is created, the "PmaCommGroup > Parameters > Communication refresh rate [ms]" configurator will be set to this value. |
Rack | (0-7) Specifies the rack number where the CPU for communication is located. Usually is 0. |
CPU Slot | (0-31) Specifies the slot number where the CPU for communication is located. (Caution: it is NOT the slot of the communication card!)
- Very often the value is 2.
- For built-in Ethernet interface (e.g. S7-1200, S7-1500, CPU1512SP ...) the value is 1. |
Create examples of testing data | A set of exemplary data is created |
Create panel for test data | Creates panel that monitors the statistics of communication values |
Panel title | Displayed in the panel header |