Preconfiguration "PmOpcUaClient - Minimal set of the PmaComm object"

Communication driver configuration PmOpcUaClient - Driver for communication with OPC UA server.

This preconfiguration can be activated when creating a new object (e.g. by "New object ..." in the context menu of the object or by pressing the Insert key after selecting the object).
 
This preconfiguration is included in the "/ Communication / Protocols and other communications / OPC" group.
 
This preconfiguration can be created in the PmaFolder, PmaRoot or PmaPrototype object.
These configurators can be set before the preconfiguration is created:
The name of created objectName of the object created in the Pma object tree.
The maximum name length is 30 characters.
This is a system name, so it must contain only alphanumeric and must not contain any diacritics (i.e. national dependent characters), empty string, spaces and first character must not be a number.
Default: "Comm"
Network addressNetwork address of the remote device (e.g. of the PLC device), to which the communication will be connected.
The address can be entered as:
- IPv4 full address (e.g. "192.168.0.15")
- IPv4 address of this computer (i.e. "127.0.0.1")
- IPv4 computer name (e.g. "server11")
- IPv4 name of this computer (i.e. "localhost")
- IPv6 full address (e.g. "2a02:c38:8136:800a:37a:ab66:6fc9:accd")
- IPv6 address of this computer (i.e. "::1")

Macro expression can be used for input (it is evaluated after the application is launched).
After the preconfiguration is created, the "PmaComm > Setting the parameters of the Ethernet-client > Network address" configurator will be set to this value.
TCP/UDP remote port numberEthernet remote port number for communication.
Communication refresh rate [ms]The period in milliseconds to be used for reading the current data by the PROMOTIC application.
After the preconfiguration is created, the "PmaCommGroup > Parameters > Communication refresh rate [ms]" configurator will be set to this value.

History:
Pm9.00.09: Created