nOper | (Long) Type of the operation with the window
0 - Close the window. The method returns true if the window has actually been closed (it was opened before that).
1 - Open the window. The method returns true if the window has actually been opened (it was closed before that).
2 - Test of opening the window. The method returns true if the window is opened. |
---|---|
sFilter | [optional] (String) Filtering text specifies which alarms are to be included into the desired output.
Different filtration fields can be used simultaneously, the alarm then must comply with all of them (e.g. "desc:FIQ100;priority.ge:5;"). The filtering text xx must not be empty string (e.g. cannot be set "desc:;"). Entries are in the KeyVal format, for example "desc:Test2;records:50;". "field:xx;" means that the corresponding alarm field must be equal to the value xx.
"field:#eq:xx;" means that the corresponding alarm field must be equal to the value xx. If the corresponding alarm field is to be equal to one of several texts, then can be entered multiple texts separated by #or:.
"field:#begin:xx;" means that the corresponding alarm field must begin with the text xx.
If the corresponding alarm field is to begin with some of several texts, then can be entered multiple texts separated by #or:. "field:#in:xx;" means that the corresponding alarm field must contain the text xx.
If the corresponding alarm field is to contain some of several texts, then can be entered multiple texts separated by #or:. "field:#le:xx;" means that the corresponding alarm field must be less then or equal to xx.
"field:#ge:xx;" means that the corresponding alarm field must be greater or equal to xx.
"area:#oper:xx;" (optional) - Displays alarms with area meets the defined operation #oper:xx. The part of the filter dependent on user setting in the alarm viewer.
For example "area:BoilerPlant1;" or "area:#eq:BoilerPlant1;" or "area:#eq:BoilerPlant1#or:BoilerPlant2;" or "area:#begin:BoilerPlant;". "s.area:#oper:xx;" (optional) - Displays alarms with area meets the defined operation #oper:xx. The part of the filter hidden from the user in the alarm viewer.
For example "s.area:BoilerPlant1;" or "s.area:#eq:BoilerPlant1;" or "s.area:#eq:BoilerPlant1#or:BoilerPlant2;" or "s.area:#begin:BoilerPlant;". "source:#oper:xx;" (optional) - Displays alarms with source meets the defined operation #oper:xx. The part of the filter dependent on user setting in the alarm viewer.
For example "source:Boiler;" or "source:#eq:Boiler;" or "source:#eq:Boiler1#or:Boiler2;" or "source:#begin:Boiler;". "s.source:#oper:xx;" (optional) - Displays alarms with source meets the defined operation #oper:xx. The part of the filter hidden from the user in the alarm viewer.
For example "s.source:Boiler;" or "s.source:#eq:Boiler;" or "s.source:#eq:Boiler1#or:Boiler2;" or "s.source:#begin:Boiler;". "desc:#oper:xx;" (optional) - Displays alarms with description (desc) meets the defined operation #oper:xx. The part of the filter dependent on user setting in the alarm viewer.
For example "desc:FIQ101;" or "desc:#eq:FIQ101;" or "desc:#eq:FIQ101#or:FIQ102;" or "desc:#begin:FIQ;". "s.desc:#oper:xx;" (optional) - Displays alarms with description (desc) meets the defined operation #oper:xx. The part of the filter hidden from the user in the alarm viewer.
For example "s.desc:FIQ101;" or "s.desc:#eq:FIQ101;" or "s.desc:#eq:FIQ101#or:FIQ102;" or "s.desc:#begin:FIQ;". "comment:#oper:xx;" (optional) - Displays alarms with comment meets the defined operation #oper:xx. The part of the filter dependent on user setting in the alarm viewer.
For example "comment:correction;" or "comment:#eq:correction;" or "comment:#eq:correction#or:test;" or "comment:#begin:correction;". "s.comment:#oper:xx;" (optional) - Displays alarms with comment meets the defined operation #oper:xx. The part of the filter hidden from the user in the alarm viewer.
For example "s.comment:correction;" or "s.comment:#eq:correction;" or "s.comment:#eq:correction#or:test;" or "s.comment:#begin:correction;". "s.usernote:#oper:xx;" (optional) - Displays alarms with usernote meets the defined operation #oper:xx. The part of the filter hidden from the user in the alarm viewer.
For example "s.usernote:correction;" or "s.usernote:#eq:correction;" or "s.usernote:#eq:correction#or:test;" or "s.usernote:#begin:correction;". "priority:#oper:xx;" (optional) - Displays alarms whose priority meets the operation #oper:xx. The part of the filter dependent on user setting in the alarm viewer.
For example "priority:5;" or "priority:#eq:5;" or "priority:#le:5;" or "priority:#ge:5;". "from:xx;" (optional) - (history only) Displays the alarms with creation time (timeon) greater or equal to time "xx". The time is entered in the form time(YYYY.MM.DD-hh:mm:ss.mmm), e.g. "from:time(2024.07.28-14:30:00.000);". The Time-range allows to narrow down the searched alarm set (alarms outside the time-range are not tested).
"to:xx;" (optional) - (history only) Displays the alarms with creation time (timeon) less then or equal to time "xx". The time is entered in the form time(YYYY.MM.DD-hh:mm:ss.mmm), e.g. "to:time(2024.07.28-15:00:00.000);".
The to time can be entered also by the now keyword, which means the current time (at the moment of calling), e.g. to:now. The Time-range allows to narrow down the searched alarm set (alarms outside the time-range are not tested). "timerange:xx;" (optional) - (history only) Displays the alarms with the creation time (timeon) belonging to specified time-range For selecting the time span by timerange, either the value of from or to must be defined, where the timerange allows to compute the missing limit of the time-range. Thus the time-range can be defined by the following pairs: from - to, from - timerange or to - timerange. For example to:now;timerange:30m;. Time-range allows to reduce the portion of alarm items to be searched (alarms outside the time-range are not tested).
The time-range can be entered as integer followed by time unit sign (without spaces). Valid time units are: w = week, d = day, h = hour, m = minute, s = second. For example timerange:12h; or timerange:90m;. |
var oAl = pMe.Pm("/Alarm");
oAl.WndHistory(1);
var oCreator = Pm.CreateView(null, "/Alarms/#history", "", "target:_blank.alarms");
oCreator.Open();