company. The supported transfer rate is
If only some selected values are to be received from the meter, then it is handy to use the
object. In this object (or by data extension
) the variables only for desired values can be defined. The value of the "
-
Reading of measured values:
There are following variables on the "
Data-received" tab:
Header of M-BUS message ActualityDuration (actuality duration [sec]),
ResponseDuration (response duration [sec]),
Energy (accumulated energy [GJ]),
Volume (accumulated volume [m3]),
Power (instantaneous power [kW]),
Flow (instantaneous flow [m3/h]),
TemperForward (Forward temperature [°C]),
TemperReturn (Return temperature [°C]),
TemperDiff (Temperature difference [°C]),
VolumeMem1 (accumulated volume [m3] from last year),
EnergyMem1 (accumulated energy [GJ] from last year),
FabricNr (Meter fabric number),
RespDurationTar1 (response duration [sec], Tariff=1),
PowerMaxTar1 (maximum power [kW], Tariff=1),
PowerMaxMem1Tar1 (maximum power [kW] from last year, Tariff=1),
FlowMaxTar1 (maximum flow [m3/h]), Tariff=1),
TemperForMaxTar1 (maximum Forward temperature [°C], Tariff=1),
TemperRetMaxTar1 (maximum Return temperature [°C], Tariff=1),
OnTime (number of days),
OnTimeErr (number of days in error),
OnTimeErrMem1 (number of days in error from last year),
DataReading (date and time of reading, year is not available),
EnergyTar2 /
EnergyTar3 /
EnergyTar4 (accumulated energy [GJ], Tariff=2/3/4),
EnergyMem1Tar2 /
EnergyMem1Tar3 /
EnergyMem1Tar4 (accumulated energy [GJ] from last year, Tariff=2/3/4),
TemperForMaxMem2Tar1 (maximum Forward temperature [°C], 1st value from last year, Tariff=1),
TemperRetMaxMem2Tar1 (maximum Return temperature [°C], 1st value from last year, Tariff=1),
FlowMaxMem2Tar1 (maximum flow [m3/h], 1st value from last year, Tariff=1),
PowerMaxMem2Tar1 (maximum power [kW], 1st value from last year, Tariff=1),
OnTimeErrMem2 (number of days in error, 1st value from last year),
EnergyMem2 /
EnergyMem2Tar2 /
EnergyMem2Tar3 /
EnergyMem2Tar4 (accumulated energy [GJ], 1st value from last year, Tariff=0/2/3/4),
VolumeMem2 (accumulated volume [m3], 1st value from last year),
Date (meter date and time),
Microprogram (version),
D0 (extended byte, perhaps always 0),
D1 (extended byte, perhaps always 0),
D2 (extended byte,
bit 0=1=preadmonition,
bit 7=0/1=installation in return/forward pipeline).