Communication with PLC devices by the Emerson company
The
Emerson company (
http://www2.emersonprocess.com) manufactures meters, sensors and also
Smart Wireless Gateways.
This device creates a
Wireless network that can be used for reading data from meters connected to such network and then pass the data forward via
OPC or
Modbus protocol for furher usage.
Communication by the Modbus protocol - Smart Wireless Gateway
The
Smart Wireless Gateway device supports
communication by the Modbus protocol.
This protocol is not set in the device as default. Therefore it is necessary to enable this protocol before the communication starts. For this communication in the PROMOTIC system can be used:
For this driver, it is recommended to set the configurators:
The
Modbus register address of analogue values starts at address
40000 (based on the documentation).
However in reality these values are available at address
0 and higher. For example the value on Modbus register at address
40010 reads in the PROMOTIC system system from address
10.